Search Results (386 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2025-13036 1 Rockwellautomation 1 Factorytalk Historian Se 2026-06-26 N/A
An authentication bypass security issue exists within FactoryTalk Historian Site Edition. By continually sending requests to the login endpoint, an attacker may obtain a valid authentication token.
CVE-2025-14272 1 Rockwellautomation 1 Factorytalk Analytics Pavilionx 2026-06-26 N/A
A security issue was identified in Pavilion due to improper authorization enforcement in API endpoints. This vulnerability can allow an unauthorized actor to execute privileged operations, including user/role management and other administrative actions.
CVE-2026-0646 1 Rockwellautomation 1 Flex I/o Ethernet/ip Adapter 2026-06-26 N/A
A denial-of-service security issue exists within the 1794-AENTR adapter due to improper memory handling of CIP protocol requests. This vulnerability can result in the adapter faulting and losing connection to its associated I/O modules, requiring a manual reset to recover.
CVE-2026-0647 1 Rockwellautomation 1 Flex I/o Ethernet/ip Adapter 2026-06-26 N/A
An improper authentication security issue exists within the 1794-AENTR adapter's embedded web server. The vulnerability allows an unauthenticated attacker to change the device's web interface password by sending a crafted HTTP GET request to a specific endpoint, without any prior authentication being required. If exploited, this could lead to unauthorized access, account takeover, and loss of the device’s embedded web server’s availability.
CVE-2026-11317 1 Rockwellautomation 2 Compactlogix, Controllogix 2026-06-16 N/A
A denial of service security issue exists in the affected product. The security issue stems from a fault occurring when a crafted CIP message is sent. Devices with less memory are more likely to be affected. This can result in a major nonrecoverable fault (MNRF). A program download is required to recover.
CVE-2025-11694 1 Rockwellautomation 1 Compactlogix 5370 2026-06-16 N/A
A security issue exists within 1769 CompactLogix controllers due to the missing validation of sequence numbers and source IP addresses in the CIP protocol. This allows attacker to abuse the exposed Connection ID’s visible on the web interface to perform denial-of-service attacks, resulting in a minor fault.
CVE-2026-9307 1 Rockwellautomation 1 Compactlogix 5370 2026-06-16 N/A
A sensitive information disclosure security issue exists within the affected CompactLogix controllers. The controller's web server exposes CIP Connection IDs on the diagnostics webpage, which are accessible to any unauthenticated user on the network. This information can be leveraged by an attacker to construct malicious packets, leading to Denial-of-Service.
CVE-2021-32926 1 Rockwellautomation 4 Micro800, Micro800 Firmware, Micrologix 1400 and 1 more 2026-06-04 5.9 Medium
When an authenticated password change request takes place, this vulnerability could allow the attacker to intercept the message that includes the legitimate, new password hash and replace it with an illegitimate hash. The user would no longer be able to authenticate to the controller (Micro800: All versions, MicroLogix 1400: Version 21 and later) causing a denial-of-service condition
CVE-2021-33012 1 Rockwellautomation 2 Micrologix 1100, Micrologix 1100 Firmware 2026-06-03 7.5 High
Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode.
CVE-2020-6990 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2026-06-03 9.8 Critical
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
CVE-2020-6988 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2026-06-03 7.5 High
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
CVE-2020-6984 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2026-06-03 9.8 Critical
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable.
CVE-2019-10955 1 Rockwellautomation 11 Compactlogix 5370 L1, Compactlogix 5370 L1 Firmware, Compactlogix 5370 L2 and 8 more 2026-06-03 6.1 Medium
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
CVE-2018-17924 1 Rockwellautomation 32 1756-en2f Series A, 1756-en2f Series A Firmware, 1756-en2f Series B and 29 more 2026-06-03 7.5 High
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
CVE-2017-7903 1 Rockwellautomation 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more 2026-06-03 9.8 Critical
A Weak Password Requirements issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected products use a numeric password with a small maximum character size for the password.
CVE-2017-7898 1 Rockwellautomation 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more 2026-06-03 9.8 Critical
An Improper Restriction of Excessive Authentication Attempts issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. There are no penalties for repeatedly entering incorrect passwords.
CVE-2016-5645 1 Rockwellautomation 6 1766-l32awa, 1766-l32awaa, 1766-l32bwa and 3 more 2026-06-03 7.3 High
Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community.
CVE-2016-2279 1 Rockwellautomation 46 Compactlogix 1756-en2f Series A, Compactlogix 1756-en2f Series A Firmware, Compactlogix 1756-en2f Series B and 43 more 2026-06-03 6.1 Medium
Cross-site scripting (XSS) vulnerability in the web server in Rockwell Automation Allen-Bradley CompactLogix 1769-L* before 28.011+ allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2015-6492 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2026-06-03 7.5 High
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service (memory corruption and device crash) via a crafted HTTP request.
CVE-2015-6490 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2026-06-03 9.8 Critical
Stack-based buffer overflow on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices through B FRN 15.003 allows remote attackers to execute arbitrary code via unspecified vectors.